Key points
- The work comes in four types: planned, reactive, emergency and deferred.
- Requests come in waves with the weather, so do the cooling start-up before the first warm days.
- NRCA recommends a roof inspection at least twice a year, in spring and fall, and after severe weather.
- Hiring a contractor for a test does not hand off the responsibility for what the report finds.
- In the worked example, planned work is about 6% of the team's hours, yet it is the part that slips.
What facility maintenance covers
Facility maintenance looks after everything in and around a building that has to keep working. For an office, a school, a clinic or a small commercial building, that comes down to seven areas:
| Area | What it includes |
|---|---|
| Heating, cooling and ventilation | Rooftop units, boilers, air handlers, exhaust fans, thermostats |
| Plumbing | Restrooms, water heaters, drains, sump pumps, backflow preventers |
| Electrical and lighting | Panels, outlets, interior and parking lot lights, the generator |
| Roof and envelope | Roof membrane, drains, gutters, walls, windows, sealants, doors |
| Fire and life safety | Fire alarm, sprinklers, extinguishers, emergency lights, exit signs, fire doors |
| Elevators | Cars, doors, phones, machine rooms |
| Grounds | Parking lots, sidewalks, landscaping, snow and ice |
On top of that sit requests, the work nobody plans: a conference room too hot, a running toilet, a stained ceiling tile. In a busy building they can outnumber the planned work orders several times over, as they do in the made-up example below. A small team stays ahead by giving the planned part a year plan and the reactive part a single queue.

All of this matters because fire alarms, sprinklers and exits have to work on the one day they are needed, a cold office or a dark stairwell lands on people at once, and a small roof leak left for a winter becomes wet insulation, a stained ceiling and a closed room.
Property maintenance is the same trade work done for an owner and the tenants who rent from them, with apartment turnovers and landlord rules on top.
Types of facility maintenance: planned, reactive, emergency and deferred
The work in a building comes in four types: planned, reactive, emergency and deferred. Types of maintenance has the full list across every setting.
Most reactive work in a building arrives as a complaint from a person, not an alarm from a machine, and it comes in waves:
You cannot plan the single calls, but you can plan for the wave. Do the cooling start-up before the warm days, not during them.
Planned work in a building is also easy to put off: skip a roof inspection and nothing happens for years, until the roof leaks over the server room. That is how deferred maintenance builds up.
Watch the direction, not the figure
The share of work that was planned (the planned maintenance percentage) has no single right figure for a building, because every light out is a small reactive job of its own. Count it every month: if it falls three months running, requests are pushing the planned work aside.
Facility maintenance plan by season, for a small team
A crew of 2 to 5 people looking after a few buildings needs a list of everything that comes due in the year, spread so that no month is buried. In Canada and the northern states, move the spring work later and the fall work earlier to suit your frosts.
| When | Planned work | Contractors to book |
|---|---|---|
| Every month | Building walk; extinguisher and emergency light checks; generator run; filters where the gauge or the calendar says | None |
| Spring (March to May) | Roof and drain inspection after winter; gutters cleared; cooling start-up on rooftop units (coils, belts, filters, condensate drains); irrigation on; parking lot walked for winter damage | Backflow test; a paving quote for crack sealing |
| Summer (June to August) | Filter changes through the cooling season; exterior paint and sealant; projects in rooms that are empty for the holidays | Sealcoating and restriping; fire alarm and sprinkler tests if they fall here |
| Fall (September to November) | Heating start-up (boilers, burners, flues, carbon monoxide alarms); second roof inspection; gutters after the leaves fall; hose bibs and irrigation drained; salt and shovels stocked | Boiler inspection where your jurisdiction requires one; snow removal contract signed |
| Winter (December to February) | Snow and ice; freeze patrol of stairwells, docks and anything with heat trace; indoor projects; next year’s budget and bids | Snow removal as it falls |
Why the roof appears twice
The National Roofing Contractors Association recommends roof inspections at least twice a year, preferably in spring and fall, and after any severe weather. The roof inspection checklist says what to look at and what counts as a fail.
Most of the other placements are common practice rather than rules: book a contractor when the contractor has slack, not in their busiest month.
The facility maintenance checklist turns this into checks for every area. The HVAC and generator checklists have the full service for those.
Contractors or your own crew
Keep frequent, quick work that needs no license with your own crew, and contract whatever needs a license, a certification, special equipment or a skill used once a year.
- Filters, belts, lamps, minor plumbing, roof walks, monthly life safety checks: your crew.
- Burner and boiler combustion work: an HVAC or boiler contractor. It is often licensed, and a fault can put carbon monoxide in the building.
- Backflow tests and panels: a certified tester and an electrician, for the certification or license.
- Refrigerant work on air conditioning: a contractor, unless your technician holds EPA Section 608 certification. EPA Section 608 rules say who may handle refrigerant.
- Fire alarm and sprinkler testing: a fire protection contractor. NFPA 72 and NFPA 25 call for qualified people; check whether your state or province licenses them.
- Elevators: the elevator contractor, for specialist mechanics and inspection by your state, province or city.
- Roofs: debris and drains in-house; repairs by a roofer. NRCA suggests the installer make repairs on a roof under warranty, to avoid conflicts with its terms.
- Paving, sealcoating, restriping: a paving contractor, for equipment and materials you do not keep.
Contracting does not hand off the responsibility
Your crew still books the visit, lets the technician in, reads the report and turns each deficiency into a job. A sprinkler report listing three corroded heads is only useful once someone replaces them.
Much of the in-house work is done off the floor, so the ladder and the lift get checked before the job, not during it. The ladder inspection checklist and the scissor lift inspection checklist say what to look at and what takes each one out of service.
Records an inspector or insurer may ask for
Keep a dated work order for each test, with the contractor’s report attached, because a fire inspector or an insurer looking at a claim usually asks the same things: when was it last tested, by whom, and what was found. Keep the records in one place, building by building.
The eleven records, and where each requirement comes fromFire and life safety, elevator, boiler, backflow, refrigerant, Legionella, energy and roof, with links to the rules
| Record | Where the requirement comes from |
|---|---|
| Monthly extinguisher inspections and the yearly maintenance date | OSHA 29 CFR 1910.157(e), where extinguishers are provided for employees; NFPA 10 |
| Emergency light and exit sign tests: 30 seconds monthly, 90 minutes yearly on battery | NFPA 101, section 7.9.3, in the edition your jurisdiction adopted; South Dakota’s test log quotes the 2000 edition |
| Fire alarm and sprinkler inspection, test and maintenance reports | NFPA 72 and NFPA 25; the contractor writes them |
| Fire door inspection, yearly | NFPA 80, section 5.2.1 in its 2007 and 2010 editions; the fire door inspection checklist covers it |
| Elevator inspection certificate and maintenance records | Your state, province or city; under ASME A17.1 the maintenance control program records are kept on site, with forms your elevator contractor provides, as Washington’s Department of Labor and Industries explains |
| Boiler inspection certificate | Your state or province, where it requires one; often inspected through your insurer |
| Backflow test reports | Your water utility or local plumbing code |
| Refrigerant leak inspection and repair records for larger systems | EPA Section 608 rules: the owner keeps them, from the paperwork your HVAC technician must hand over after each visit |
| A water management program for Legionella, where the building needs one | The CDC’s water management toolkit, based on ASHRAE Standard 188 |
| Energy use reports | Where a city or state requires benchmarking; dozens of state and local governments build their programs and laws on EPA’s ENERGY STAR Portfolio Manager |
| Roof inspections with photos | NRCA advises filing written notes and photos so each inspection can be compared with the last |
This list is information, not legal advice. Your fire marshal, building department and insurer decide what applies to your building; in Canada, your province’s fire code and its boiler and elevator safety authorities.
Facility maintenance workload example: three buildings, three people
ExampleA year of planned work and requests
A made-up team of three (Susan Clarke leads, with technicians Jason Miller and Andre Dubois) looks after an office building, a retail building and a small warehouse. Every number is invented.
Eleven planned routines, from rooftop unit services to letting contractors in, come to 196 work orders and 328 hours a year. Requests are bigger: about 25 a week, 1,250 a year, averaging 1.5 hours each with travel.
3 people × 1,800 hours
2,203 of 5,400 hours
Projects, tenant moves, snow, parts runs and driving take most of the rest.
The planned work, routine by routineEleven routines, 196 work orders: 328 hours a year
| Planned routine | How many | Times a year | Hours each | Hours a year |
|---|---|---|---|---|
| Rooftop unit service | 9 units | 4 | 1.5 | 54 |
| Boiler check in heating season | 1 | 7 | 1 | 7 |
| Life safety walk: extinguishers, exits, emergency lights | 3 buildings | 12 | 1.5 | 54 |
| Emergency lights, 90-minute test | 3 buildings | 1 | 3 | 9 |
| Generator run | 1 | 12 | 1 | 12 |
| Building walk-through | 3 buildings | 12 | 2 | 72 |
| Roof inspection | 3 roofs | 2 | 2 | 12 |
| Gutters and roof drains | 3 roofs | 2 | 3 | 18 |
| Heating and cooling changeovers | 3 buildings | 2 | 6 | 36 |
| Parking lot and grounds check | 3 lots | 12 | 0.5 | 18 |
| Contractor visits: let in, escort, read the report | 12 visits | 1 | 3 | 36 |
| Total | 196 work orders | 328 |
The planned work is about 6% of the team’s hours, yet it is the part that slips, because a request always has a person waiting and a roof inspection never does. So give it fixed days: the life safety walk on the first Monday of the month in each building, the rooftop units in the second week of each quarter, the roof in the second week of April and October. Requests fill the rest of the week.
How Maintensor fits a building team
The facility maintenance software page shows this setup in a demo office building:
- Buildings. Each is a location, with its floors, suites and mechanical rooms inside it.
- Equipment. Four identical rooftop units can be one asset with four units, each with its own status and its own work.
- Planned routines. Each is a work order set to repeat, and when one is completed the next is created on its schedule.
- Contractors. A contractor’s report can be attached to the work order as a PDF.
- Requests. Staff and tenants are invited as requesters, free on every plan, and report a problem from their phone’s browser. An admin turns each request into a work order or declines it with a reason. On Pro and Max, a requester who scans the QR label on a piece of equipment or a room gets Report a problem with it filled in.
What it does not do
Requesters need that invitation: there is no public form, and a request carries no photo. It does not read meters or building controls, track energy use, or certify any inspection. It records what was done, when and by whom.