Generator maintenance checklist

A generator maintenance checklist covers what keeps a standby generator ready to carry the building: a weekly walk-around, a monthly run under load for at least 30 minutes, and yearly service of the fuel, batteries, coolant and transfer switch.

Free, no sign-up. Print it, or type into the Word file.

By MaintensorUpdated

Page 1 of the blank generator maintenance checklist: the generator and visit, then the weekly inspection and the monthly run under load, each check with a box for OK and Fail and a line for a note.
Page 1 of 2

The checks, by visit

One sheet per generator and visit: the weekly inspection, the monthly run under load, or the yearly service. A failed check gets a work order, and the maker’s manual can ask for more than this list.

Weekly inspection7 checks

  • Fuel: main and day tank levels, day tank float switch, piping and hoses, tank vents
  • Oil level; oil heater, where fitted
  • Coolant level, block heater warm, belts, hoses, radiator fan
  • Exhaust: condensate trap drained, joints and supports
  • Starting batteries: terminals, electrolyte level (vented types), charger output
  • Control switch in Auto, no alarm lamps lit
  • Engine and generator: guards on, nothing loose, nothing stored in the room or enclosure

Monthly run under load9 checks

  • Start the test by simulating an outage with the transfer switch's test switch; with several switches, start from a different one each month
  • Time from simulated outage to power on the emergency loads
  • Run at least 30 minutes under load, warm-up and cool-down not counted
  • Diesel load: kW reading against 30 percent of the standby nameplate rating, or exhaust temperature against the maker's minimum
  • Readings during the run: oil pressure, coolant temperature, voltage, frequency, hour meter at start and stop
  • Exhaust smoke
  • Transfer back to normal power after its time delay, then the unloaded cool-down run
  • Transfer switch looked over: connections, signs of heat, contact wear, dust, covers closed
  • Control back in Auto, alarms reset, no leaks after the run

Yearly, and every three years8 checks

  • Load bank test for a diesel set whose monthly runs do not reach 30 percent or the exhaust temperature: at least 50 percent of nameplate for 30 minutes, then at least 75 percent for 60 minutes
  • Fuel quality test, using ASTM methods; water drained from the tank bottom
  • Maker's service: oil and filters, fuel filters, air filter, coolant tested, belts and hoses
  • Starting batteries load tested or replaced by age
  • Engine safety shutdowns proved: low oil pressure, high temperature, overspeed, overcrank
  • Circuit breakers in a Level 1 system exercised, with the generator off
  • Transfer switch: infrared scan under load, then cleaned and tightened with it de-energized, by a qualified electrician
  • Every 36 months, Level 1 systems: a continuous run for the system's class, up to 4 hours, a diesel at no less than 30 percent of nameplate
What counts as a fail, check by checkThe full tables, and the NFPA 110 section behind each check.

“NFPA 110” gives the section in the 2010 edition, the one the 2012 Life Safety Code references; later editions may number some sections differently. “Maker” means the manual decides. “Practice” means common practice.

Weekly inspection

NFPA 110 (8.4.1) requires the emergency power supply to be inspected weekly. The lines follow the list in Minnesota’s Department of Health guidance.

Check Fail if Basis
Fuel: main and day tank levels, day tank float switch, piping and hoses, tank vents Below the level your run-time plan needs, any leak, a blocked vent NFPA 110 (8.4.1); Maker
Oil level; oil heater, where fitted Below the mark, oil under the engine Maker
Coolant level, block heater warm, belts, hoses, radiator fan Low coolant, a cold block, a cracked hose or belt Maker
Exhaust: condensate trap drained, joints and supports Soot at a joint, a loose support, water in the trap Maker
Starting batteries: terminals, electrolyte level (vented types), charger output Corrosion, low electrolyte, a charger fault or no charge NFPA 110 (8.4.1); Maker
Control switch in Auto, no alarm lamps lit Switch left in Off or Manual, any alarm Practice
Engine and generator: guards on, nothing loose, nothing stored in the room or enclosure Debris, loose fittings, blocked air louvers Maker

Monthly run under load

Check Fail if Basis
Start the test by simulating an outage with the transfer switch’s test switch; with several switches, start from a different one each month Generator does not start, or the switch does not transfer NFPA 110 (8.4.3); rotating is NFPA handbook advice Minnesota quotes
Time from simulated outage to power on the emergency loads Longer than the system’s type: 10 seconds for a Type 10 system, which NFPA 101 expects for emergency lighting NFPA 110; NFPA 101
Run at least 30 minutes under load, warm-up and cool-down not counted Shorter than 30 minutes NFPA 110 (8.4.2)
Diesel load: kW reading against 30 percent of the standby nameplate rating, or exhaust temperature against the maker’s minimum Neither reached: plan the yearly load bank test NFPA 110 (8.4.2)
Readings during the run: oil pressure, coolant temperature, voltage, frequency, hour meter at start and stop Outside the maker’s range NFPA 110; Maker
Exhaust smoke Continuous black smoke, which NFPA 110’s annex describes as a sign of wet stacking NFPA 110
Transfer back to normal power after its time delay, then the unloaded cool-down run Will not retransfer, or shuts down without at least 5 minutes of unloaded cool-down (small air-cooled sets excepted) NFPA 110 (6.2.10, 8.4.5, 8.4.6)
Transfer switch looked over: connections, signs of heat, contact wear, dust, covers closed Discolored terminals, heavy pitting, a cover off NFPA 110 (8.3.5)
Control back in Auto, alarms reset, no leaks after the run Left in Off or Manual Practice

Yearly, and every three years

Check Fail if Basis
Load bank test for a diesel set whose monthly runs do not reach 30 percent or the exhaust temperature: at least 50 percent of nameplate for 30 minutes, then at least 75 percent for 60 minutes Cannot hold the load, overheats, alarms NFPA 110 (8.4.2.3)
Fuel quality test, using ASTM methods; water drained from the tank bottom Water, sludge or a failed result NFPA 110 (8.3.8); Maker
Maker’s service: oil and filters, fuel filters, air filter, coolant tested, belts and hoses Anything past its hours or age in the manual Maker
Starting batteries load tested or replaced by age Fails the test, or past the maker’s service life Maker
Engine safety shutdowns proved: low oil pressure, high temperature, overspeed, overcrank A shutdown that does not trip Maker
Circuit breakers in a Level 1 system exercised, with the generator off A breaker that will not operate NFPA 110 (8.4.7)
Transfer switch: infrared scan under load, then cleaned and tightened with it de-energized, by a qualified electrician Hot spots, loose connections, worn contacts Practice
Every 36 months, Level 1 systems: a continuous run for the system’s class, up to 4 hours, a diesel at no less than 30 percent of nameplate Cannot finish the run NFPA 110 (8.4.9)

Minnesota’s guidance recommends the yearly infrared scan of transfer switches; infrared thermography explains what the camera finds and what it misses.

A run log, with the arithmetic

Minnesota’s guidance lists what a monthly test record should hold. Here it is as a log, one line per monthly run.

ExampleA 200 kW diesel generator, March to May

Made-up figures.

Date Initials Transfer switch Transfer time (s) Hours start Hours stop Load (kW) Oil pressure (psi) Coolant (°F) Notes
Mar 4 KB ATS-1 8 412.6 413.2 46 52 182 None
Apr 1 KB ATS-2 9 413.2 413.8 44 52 181 Light black smoke
May 6 GT ATS-1 8 413.8 414.4 47 51 183 Battery terminal cleaned

The target. 30 percent of the 200 kW standby rating is 60 kW. Use the standby rating, not the prime rating: NFPA 110’s annex points out that a 100 kW standby set is often rated 80 kW for prime power, which would wrongly lower the target.

The shortfall. This building’s emergency loads draw 44 to 47 kW, so the monthly runs count only if the exhaust reaches the maker’s minimum temperature, and the April smoke says it may not. The yearly load bank test is then at least 100 kW for 30 minutes and 150 kW for 60 minutes.

The hours. Each run is 0.6 hours on the meter, which includes warm-up and cool-down. Twelve of them plus the load bank test come to about 9 hours a year, far inside the 100 hours EPA allows for maintenance and testing under 63.6640(f).

When a real outage counts

A real outage or peak load shaving can stand in for the monthly run if the set runs as the test requires and the data are recorded, as Minnesota’s guidance explains. But EPA’s engine rule, 40 CFR 63.6640(f), does not allow an emergency engine to be used for peak shaving.

Before you start

Who does it
Your building technician can do the weekly inspection and the monthly run. The dealer or a trained technician does the yearly service and load bank test, and a qualified electrician works inside the transfer switch.
Use the test switch
Start the monthly run with the transfer switch’s test switch, not by opening the main breaker, which exposes the person doing it to shock and arc flash. Minnesota’s guidance recommends adding a test switch where there is none.
Warn and stand clear
Warn the building before power transfers. Exhaust is hot and carries carbon monoxide, and fans and belts can start on their own while the control is in Auto.

When a check fails

A generator that will not start, will not transfer or will not carry its load is out of service for the next outage, not just this test. Make it a High priority work order the same day.

If the generator feeds life safety loads such as exit lighting, tell whoever needs to know and line up temporary power as your authority having jurisdiction expects.

NFPA 110 asks that testing and maintenance be overseen by a properly trained person, as Minnesota’s Department of Health guidance sets out. This list is a starting point, not a substitute for training or the maker’s manual, which can ask for more.

Add it to an inspection calendar

Put these checks, and the rest of the building's, on a year plan with the usual minimums for the United States or Canada, then print it or add it to your calendar: open the inspection calendar with emergency generator ticked.

What NFPA 110 requires

NFPA 110, the standard for emergency and standby power systems, applies when another code points to it: the 2012 edition of NFPA 101 does that for generators that power emergency lighting, as Minnesota’s guidance explains. Which edition applies, and to which generator, is for your authority having jurisdiction to say.

In Canada the 30 minutes are not enough: CSA C282, which the National Fire Code calls on (2020, 6.5.1.1), asks for a monthly run of at least 60 minutes at 30% of rated load or more, through every transfer switch, and a full-load test every year, as the Weyburn Fire Department’s summary gives them.

The standard in shortLevels 1 and 2, what NFPA 110 requires, NFPA 99 in health care, and CSA C282 in Canada.

NFPA 110 sorts systems into Level 1, where a failure could cost lives or cause serious injury, and Level 2, for less critical loads. In short, it requires:

  • a written schedule of maintenance and testing;
  • a weekly inspection and a monthly run under load;
  • monthly operation of every transfer switch;
  • yearly fuel testing;
  • a written record of every inspection, test and repair, ready for the authority having jurisdiction.

Health care facilities under the 2012 edition of NFPA 99 test 12 times a year, 20 to 40 days apart. In Canada, CSA C282 covers emergency generators in buildings where the National Building Code requires emergency power, as your province adopts it.

The National Fire Code of Canada also asks for the fuel to be renewed within 12 months (2020, 6.5.1.5).

This page is information, not a substitute for the standard, and a record of tests does not make a system compliant.

Generator tests in Maintensor: the run log as Number steps

Set the generator up as an asset with its nameplate, and its transfer switches as assets with the generator as their parent asset, so their history sits together. Build three procedures: weekly, monthly and yearly. Attach the load bank contractor’s report and the fuel lab’s results to the yearly work order as files.

  • Every reading in the run log becomes a Number step, named with its unit and target because a Number step has no limits of its own: “Load, kW (target 60)”. Each check becomes an Inspection check, and “Control back in Auto” a required one.
  • For the monthly run, a repeat of every 4 weeks puts each due date 28 days after the last, which suits a test window like NFPA 99’s. A monthly repeat on a weekday, such as the first Tuesday, works as well.
  • A check answered Fail needs the finding and a photo before moving on, then offers a follow-up work order and Mark asset down, so the generator shows as Down until someone sets it back.
Preventive maintenance software in Maintensor: a work order's repeat form set to every 4 weeks on Wednesday, with its next five due dates.
A work order's repeat form set to every 4 weeks on Wednesday, with its next five due dates.

What it does not do: oil changes at so many run hours cannot come due from the hour meter. Work comes due by the calendar only, which is time-based maintenance; the hour meter is recorded in a Number step, and someone has to read it.

Each reading also lives only on its own work order, so the log above is built by opening past work orders. For a building with several generators and switches, the facility maintenance software page shows the setup, and the electrical inspection checklist covers the panels the generator feeds.

Questions

What people also ask.

More in the checklists, or see the whole product on the features page.

How long should a standby generator run each month?

NFPA 110 asks for at least 30 minutes a month under load. A diesel set must carry enough load to hold the maker's minimum exhaust temperature, or run at operating temperature at no less than 30 percent of its nameplate kW rating. A gas or propane set runs on whatever building load is available. Warm-up and cool-down time does not count toward the 30 minutes.

What is a generator load bank test, and when is it needed?

A load bank is a portable bank of resistors that gives a generator an artificial load. Under NFPA 110, a diesel set whose building load is too light for the monthly run is exercised monthly on that load, then once a year on a load bank: at least 50 percent of nameplate for 30 minutes, then at least 75 percent for 60 minutes. Light loading leaves unburned fuel in the exhaust, called wet stacking.

Does NFPA 110 apply to every standby generator?

NFPA 110 applies where another code requires an emergency or standby power system, for example NFPA 101 for generators that power emergency lighting, or NFPA 99 in health care. A generator kept only so the business can keep working may not be covered. Your authority having jurisdiction decides, but the NFPA 110 routine is a sound model either way.

How many hours a year can an emergency generator run for testing?

Under EPA's engine rule, 40 CFR 63.6640(f), an emergency stationary engine may run up to 100 hours a calendar year for maintenance checks and readiness testing, with no limit during real emergencies. Twelve 30 minute monthly runs and a 90 minute load bank test come to 7.5 hours. State air permits can set their own limits, so check yours.

Run one building through it.

Start the trial, add one building with its floors, rooftop units and boiler, and invite the people who report problems as requesters, free on every plan.

30-day free trial. No credit card.