The checks, by area
One sheet per roof and visit, for single-ply (TPO, PVC, EPDM), built-up, modified bitumen and metal panel roofs. Water still standing 48 hours after rain is a fail, and so is anything that can let water in: each becomes a work order with a photo and a due date.
Access, edges and skylights4 checks
- Hatch or roof door
- Guardrails (OSHA 1910.29) and anchors (maker's manual)
- Skylights (OSHA 1910.28(b)(3))
- Walkway pads to equipment
The field of the roof8 checks
- Standing water
- Membrane surface
- Blisters and wrinkles
- Built-up and modified bitumen
- Ballast
- Underfoot
- Metal panels
- Debris
Seams, flashing and penetrations6 checks
- Seams and laps (run a blunt, rounded tool along them)
- Base flashing at walls, parapets and curbs
- Counterflashing, coping and edge metal
- Pipe boots and vents
- Pitch pans
- Expansion joints
Drains, scuppers and gutters3 checks
- Roof drains
- Overflow drains and scuppers
- Gutters and downspouts
Rooftop equipment and curbs6 checks
- Equipment curbs
- Access panels
- Condensate lines
- Kitchen exhaust fans
- Pipe and conduit supports
- Equipment no longer used
From inside, below the roof4 checks
- Ceiling tiles and the underside of the deck
- Roof drain pipes inside
- Top-floor walls under parapets
- Leaks reported since the last round
What counts as a fail, check by checkThe full tables, area by area.
Every line is common practice, to adjust with your roof maker’s guide, unless a rule or NRCA is named.
Access, edges and skylights
| Check | Fail if |
|---|---|
| Hatch or roof door | Will not stay open, or is left unlocked |
| Guardrails (OSHA 1910.29) and anchors (maker’s manual) | A rail loose or missing; an anchor damaged or corroded |
| Skylights (OSHA 1910.28(b)(3)) | Cover or screen missing, cracked or loose |
| Walkway pads to equipment | Missing, loose, or the membrane beside them worn |
The field of the roof
| Check | Fail if |
|---|---|
| Standing water | Still there 48 hours after rain, in drying weather (NRCA’s definition of ponding) |
| Membrane surface | Punctures, cuts, splits, or worn through near equipment |
| Blisters and wrinkles | New, larger than in the last photos, or split open |
| Built-up and modified bitumen | Bare spots where gravel or granules are gone; cracking |
| Ballast | Stone or pavers blown off or piled up; bare membrane showing |
| Underfoot | A soft or spongy spot, which may be wet insulation |
| Metal panels | Rust through, loose or missing fasteners, open laps |
| Debris | Branches, trash, screws and cut-offs: bag them and take them down |
A puddle the morning after rain is not yet a fail; one still there on the third day is. NRCA’s roofing manual uses the same 48 hours to judge whether a roof drains properly.
Seams, flashing and penetrations
| Check | Fail if |
|---|---|
| Seams and laps (run a blunt, rounded tool along them) | The tool slips in, or an edge lifts |
| Base flashing at walls, parapets and curbs | Pulled away, split at a corner, or sagging |
| Counterflashing, coping and edge metal | Loose, lifted, open joints, missing fasteners or sealant |
| Pipe boots and vents | Split boot, loose clamp, open top |
| Pitch pans | Filler shrunk away from the pipe, or cracked |
| Expansion joints | Cover torn or pulled loose |
Drains, scuppers and gutters
| Check | Fail if |
|---|---|
| Roof drains | Strainer dome missing or broken; debris in the bowl; clamp ring loose |
| Overflow drains and scuppers | Blocked, or stains below showing water has run through them |
| Gutters and downspouts | Blocked, pulling away, leaking at the joints |
Rooftop equipment and curbs
| Check | Fail if |
|---|---|
| Equipment curbs | Flashing open at corners; curb rusted or rotted |
| Access panels | Loose or missing; screws lying on the membrane |
| Condensate lines | Broken, or draining onto a seam |
| Kitchen exhaust fans | Grease on the membrane, which damages some membranes (ask the maker) |
| Pipe and conduit supports | On bare membrane, sunk in, or cutting it |
| Equipment no longer used | A dead unit, curb or pipe left on the roof: the roofer removes it and patches |
The service on the units themselves is in the HVAC maintenance checklist.
From inside, below the roof
| Check | Fail if |
|---|---|
| Ceiling tiles and the underside of the deck | Stains, wet tiles, rust or drips |
| Roof drain pipes inside | Drips at the drain body or the joints |
| Top-floor walls under parapets | Stains, peeling paint, white salt deposits |
| Leaks reported since the last round | Any not yet traced to a cause on the roof |
Mark every finding on the plan by its column line. A stain at D-7 inside and an open curb flashing near D-7 on top are one problem, not two.
A warehouse roof’s year, and a winter of leaks
ExampleOne roof, 19 person-hours, three drips
A made-up distribution warehouse: one single-ply roof of 120,000 square feet (about 11,000 m²), 12 drains, 2 overflow scuppers, 6 rooftop units and one hatch. Kevin Brooks and Tyler Jensen do the rounds. Every number is invented to show the arithmetic.
| Visit | People | Hours | Person-hours |
|---|---|---|---|
| Spring inspection, April | 2 | 3 | 6 |
| Fall inspection, October | 2 | 3 | 6 |
| Drains after the leaves fall | 2 | 1 | 2 |
| After a June windstorm | 2 | 1.5 | 3 |
| Escorting the roofer, 2 visits | 1 | 2 | 2 |
| Total | 19 |
The drips. That winter, three are reported: in December on racking near column D-7, in January on the floor by the same rack row, and in February after a thaw, one bay over at D-8. Each is mopped up and written down with its column line, so the spring inspection starts at D-7.
The cause. It finds the base flashing on the uphill side of rooftop unit 4’s curb pulled away for about 10 inches: water ran along the deck under the membrane and came through at the low points. The installer repairs it under the warranty.
Without the log, it would have been three mop-ups and a fourth leak in March.
After a storm: wind, hail and heavy snow
Wait until the roof is safe to walk, and start inside, where the ceiling shows what the roof let through.
- Wind. Edge metal and coping lifted, membrane loose at corners, ballast moved, units shifted on their curbs.
- Hail. Dents in metal panels, caps and unit fins; bruises or cracks in the membrane, which a roofer should confirm.
Heavy snow
FEMA’s snow load safety flyer lists warning signs of an overstressed roof, among them sagging ceiling tiles, sprinkler heads dropping below the ceiling, popping or creaking noises, sagging metal decking, doors and windows that no longer open or close, cracks in walls, severe leaks, and water collecting where it does not drain on a low-slope roof.
If any appear, FEMA says to evacuate promptly and have the local building authority or a qualified design professional inspect the structure. It calls snow removal dangerous and only for qualified people; OSHA’s rooftop snow removal guide covers the hazards to workers.
Who fixes what
Your crew clears debris, strainers, drains and gutters; repairs to a roof under warranty go to the roofer who installed it. A roof near the end of its life belongs on the capital list with a date and a price, not on a pile of patch work orders; deferred maintenance covers deciding what can wait.
Who fixes what on a commercial roofInspections, warranty repairs, temporary patches, leaks at a unit's curb, and snow.
| Work | Who |
|---|---|
| Debris, strainers, drains and gutters | Your crew |
| Spring, fall and storm inspections | Your crew, or a roofer for a roof you cannot judge |
| Repairs to a roof under warranty | The roofer who installed it, as NRCA advises, to avoid conflicts with the warranty |
| A temporary patch while it still rains | Your crew, if the warranty allows; tell the roofer that day |
| A leak at a unit’s curb | The roofer for the flashing, the HVAC contractor for the unit |
| Snow removal | Qualified people only, as FEMA says |
Before you start
When a check fails
An active leak comes first: protect what is under it, call the roofer the same day, and mark the spot on the roof and on the ceiling. Anything else (an open seam, a split pipe boot, a drain that holds water) becomes a work order with a photo and a due date.
This roof inspection checklist is a starting point to adapt with your roof maker’s care guide and warranty, not a substitute for training, a roofer or the rule.
Fall protection: what OSHA requires
In OSHA’s general industry rules, a low-slope roof has a slope of 4 in 12 or less (29 CFR 1910.21), and work on one falls under 1910.28(b)(13), by distance from the edge. Less than 6 feet (about 1.8 m) from the edge, that means a guardrail, safety net, travel restraint or personal fall arrest system.
The fall protection rules in fullEach distance from the edge, warning lines, skylights, training, pitched roofs, and the rules in Canada.
- Less than 6 feet (about 1.8 m): a guardrail, safety net, travel restraint or personal fall arrest system.
- 6 feet to less than 15 feet (4.6 m): the same, but a designated area may be used for work that is both infrequent and temporary.
- 15 feet or more: one of those systems or a designated area, or none for work that is both infrequent and temporary; in every case the employer must implement and enforce a work rule that nobody goes within 15 feet of the edge without fall protection.
A designated area is marked by a warning line, which 1910.29(d) sets at 34 to 39 inches (86 to 99 cm) high and at least 6 feet from the edge for temporary and infrequent work, 15 feet for other work.
Skylights count as holes: 1910.28(b)(3) requires protection from falling through any hole 4 feet (1.2 m) or more above a lower level, and 1910.29(e) requires a cover to hold twice the load that may be put on it and be secured in place. Anyone who uses personal fall protection must first be trained by a qualified person (1910.30(a)).
1910.28(a)(2)(ii) leaves out inspecting conditions before work starts or after it ends, except where fall protection meeting 1910.29 is installed and available; whether your rounds fit that is for your safety lead to decide from the rule’s text.
Pitched roofs. Smaller buildings often have a pitched roof of shingles or metal. Steeper than 4 in 12, it is not low-slope, and 1910.28(b)(1) requires protection on any walking-working surface with an unprotected side or edge 4 feet (1.2 m) or more above a lower level.
Common practice is to look from the ground with binoculars and from a ladder at the eave, and leave walking it to a roofer. Look for missing or curled shingles, granules in the gutters, lifted flashing and a sagging ridge. The apartment maintenance checklist puts this look on its spring and fall rounds.
This is a summary, for information: read the rule that applies to you. A reroof or other construction work falls under OSHA’s construction rules, 29 CFR part 1926. In Canada, each province sets its own fall protection rules. The fixed ladder and the hatch have their own checks in the ladder inspection checklist.
Roof inspections in Maintensor: one location per roof section
Make the roof a location under its building, and each section of a large roof a location under that; rooftop units are assets there. There is no library of ready-made checklists, so build this one once as a procedure.
- The steps. A Heading step for each area, an Inspection check (Pass, Flag or Fail) for each line, and a Photo step per roof section.
- The repeats. Attach it to a work order on the roof that repeats monthly, every 6 months, on a date (April, then October); the next one is created when the current one is completed. Repeats run by the calendar only, so the after-storm visit is a work order you create by hand, with a shorter copy of the procedure.
- A failed check. The inspector adds a note and a photo before moving on and can create a follow-up work order for the roofer; attach the roofer’s report to it as a PDF.

People under the roof can report a drip as requesters, free on every plan. A request takes no photo, so ask them to write the column line under Any detail, and give the leak’s work order the roof section as its location: the list filtered by that location then shows every leak and repair it has had.
Only Admins and Full users answer checklists, so the inspectors need user seats; the roofer does not. The building’s other rounds are in the facility maintenance checklist, and how they fit together is on the facility maintenance software page.