Commercial HVAC maintenance checklist

A commercial HVAC maintenance checklist lists what to inspect, measure and service on rooftop units, air handlers and exhaust fans: monthly filter and drain checks, a quarterly service, and a start-up each spring and fall.

Free, no sign-up. Print it, or type into the Word file.

By MaintensorUpdated

Page 1 of the blank HVAC maintenance checklist: the unit and visit, six readings with last visit's beside them, and the monthly and quarterly checks, each with a box for OK and Fail and a line for a note.
Page 1 of 2

The checks, by visit

One sheet per unit and visit. Tick each check on the visit it belongs to; anything that fails gets a work order the same day, with the reading in it. Add each unit’s own tasks from its manual, and where the two disagree, the manual wins.

Monthly6 checks

  • Filters: look at the bank, read the gauge
  • Condensate drain pan, trap and line
  • Condensate float switch, where fitted: lift it
  • Cabinet: panels on, no oil at refrigerant joints
  • Running: noise, vibration, alarms, space near setpoint
  • Split system condenser clear, line set insulation intact

Quarterly7 checks

  • Filter pressure drop recorded, change-out date checked
  • Fan belts: tension, wear, sheave alignment
  • Fan and compressor amps, voltage at the disconnect
  • Outdoor air dampers and actuators open and close
  • Evaporator and condenser coils
  • Contactors and terminals (unit locked out)
  • Space around the unit and its access panels

Exhaust fans4 checks

  • Runs when scheduled; backdraft damper opens and closes
  • Belt, pulleys, bearings and motor
  • Wheel and housing
  • Bird screen, curb and roof flashing

Spring start-up: cooling9 checks

  • Crankcase heaters on for the time in the manual
  • Condenser coil washed, fins combed
  • Drain pans cleaned and checked for growth
  • Outdoor air intake louvers and bird screens
  • Run capacitors measured
  • Contactor and condenser fan motor
  • Refrigerant circuit checked by a certified technician
  • Economizer changes over and modulates; sensors read sensibly
  • Cooling readings taken (page 1)

Fall start-up: heating10 checks

  • Heat exchanger: no cracks, holes or rust-through
  • Burners clean, flame even, ignition and flame sensing work
  • Flue, inducer fan and combustion air inlet clear
  • Safety limits tested as the manual describes
  • Gas pressure to the rating plate (qualified gas technician)
  • Temperature rise recorded
  • Carbon monoxide alarms where fuel is burned
  • Electric heat and heat pumps: amps, reversing valve, defrost
  • Freeze protection: freezestats, heat tape
  • Belts and intake louvers again
What counts as a fail, check by checkThe full tables, and where each interval comes from.

“62.1” marks a minimum frequency from ASHRAE Standard 62.1’s maintenance table, explained under the standards below. “Maker” means the unit’s manual decides. “Practice” means common practice, to adjust.

Monthly

For every rooftop unit, air handler and split system.

Check Fail if Basis
Filters: look at the bank, read the gauge where there is one At or past the change-out figure, collapsed or wet media, gaps around the frames Maker; 62.1 sets quarterly as the minimum
Condensate drain pan, trap and line Standing water, slime, a dry or blocked trap, water on the cabinet floor Practice
Condensate float switch, where fitted: lift it The unit keeps running with the float raised Practice
Cabinet: panels on and fastened, no oil at refrigerant joints A missing panel, water inside, an oily film at a joint (a sign of a leak) Practice
Running: noise, vibration, controller alarms, space near setpoint A new squeal or rattle, an alarm, a zone out of range Practice
Split system condensers: clear of leaves and stored items, line set insulation intact Blocked airflow, less clearance than the manual asks, torn or missing insulation Maker

Quarterly

Check Fail if Basis
Filter pressure drop recorded, and the replacement date checked Above the change-out figure, or past its date 62.1
Fan belts: tension, wear, sheave alignment Cracked, glazed or frayed belt; deflection outside the manual’s figure; sheaves out of line Maker; 62.1 sets twice a year
Fan and compressor amps on each leg, voltage at the disconnect Over nameplate, or outside the voltage range Maker
Outdoor air dampers and actuators: command them open and closed Stuck, partly open when commanded closed, linkage slipping on its shaft Practice; 62.1 sets yearly
Evaporator and condenser coils Dirt visible across the face, matted or flattened fins, oil staining Practice; 62.1 sets yearly
Contactors and terminals, with the unit locked out Pitted or burnt contacts, discolored wire insulation, loose terminals 62.1 sets yearly
Space around the unit and its access panels Anything stored in it, a blocked path to the unit 62.1

Exhaust fans

Roof and wall exhaust fans, on the quarterly round.

Check Fail if Basis
Fan runs when scheduled; backdraft damper opens and closes Not running, or the damper stuck either way Practice
Belt, pulleys, bearings and motor Worn or loose belt, noisy or hot bearings, grease leaking Maker
Wheel and housing Built-up grease or dirt on the blades, wobble 62.1 sets yearly for fan blades
Bird screen, curb and roof flashing Torn screen, nest, loose curb, gaps in the flashing Practice

Spring start-up: cooling

Check Fail if Basis
Crankcase heaters on for the time the manual gives before the compressor starts Heater cold, or no time given before start Maker
Condenser coil washed, fins combed Coil still blocked after cleaning Maker
Drain pans cleaned and checked for growth Slime or growth left, or water carried past the pan 62.1 (yearly)
Outdoor air intake louvers and bird screens Debris, nests or damage that blocks the intake 62.1 (twice a year)
Run capacitors measured Outside the tolerance printed on the capacitor, bulging or leaking Maker
Contactor and condenser fan motor Pitted contacts; fan amps over nameplate; a cracked blade Maker
Refrigerant circuit checked by a certified technician Outside the maker’s charging chart, or a leak found Maker; EPA Section 608
Economizer changes over and modulates; outdoor and return air sensors read sensibly Stuck dampers, a sensor far off a hand thermometer 62.1 (yearly for the controls)
Cooling readings from the table above Any fail limit Maker

Fall start-up: heating

Check Fail if Basis
Heat exchanger inspected for cracks, holes and rust-through Any crack or hole: shut the gas off and tag the unit Maker
Burners clean, flame even, ignition and flame sensing work Lazy, lifting or yellow flame; delayed ignition; failed flame proving Maker
Flue, inducer fan and combustion air inlet clear Blocked, rusted through or disconnected Maker
Safety limits (high limit, rollout switch, pressure switch) tested as the manual describes Burner keeps firing when a limit opens Maker
Gas pressure set to the rating plate, by a qualified gas technician Outside the plate Maker
Temperature rise recorded Outside the range on the rating plate Maker
Carbon monoxide alarms in rooms with fuel-burning equipment No alarm, or it fails its test Practice
Electric heat and heat pumps: amps on each stage, reversing valve and defrost A stage drawing nothing or over nameplate; no change to heating; no defrost Maker
Freeze protection: freezestats on water coils, heat tape on rooftop drain lines A freezestat that does not trip, cold heat tape Practice
Belts and intake louvers again As in spring 62.1 (twice a year)

The readings, with a filled-in example

A tick says someone looked; a reading says what they found, and the next one says whether it is changing. Take these at every quarterly service and both start-ups, with the outdoor temperature.

Supply and return air, coolingFlag a split well away from the unit's usual figure at similar weather, say 5°F (3°C) either way.
Filter pressure dropFail at the filter maker's change-out figure; flag near zero (a missing filter, or air going around the bank).
Motor and compressor amps, each legFail above the nameplate's full-load or rated-load amps; flag one leg well off the others.
Temperature rise, heatingFail outside the range on the unit's rating plate.
Refrigerant pressures, superheat or subcoolingCertified technician only. Fail outside the maker's charging chart, or any sign of a leak.

ExampleOne rooftop unit, May to August

Made-up readings. The filter’s change-out figure is 0.8 inches of water column (about 200 Pa); the compressor’s nameplate says 18.6 rated-load amps.

Visit Outdoor Split Filter drop Compressor amps
May 82°F 19°F 0.35 in. 15.2
June 84°F 19°F 0.48 in. 15.4
July 83°F 24°F 0.92 in. 15.0
August 84°F 13°F 0.30 in. 13.1

July. The filters were past their change-out figure and the split jumped: less air crossed the coil, so it came off colder, and a starved coil can ice up. New filters went in that day.

August. The split fell and the compressor drew less current, which points to a low charge. The certified technician found a leak at a brazed joint. A column of ticks would have shown four good months.

Before you start

Certified work
Anything that opens the refrigerant circuit needs a certified refrigeration technician; gas heat needs whoever your state or province licenses for gas work.
Lock it out
Lock out and tag out the unit’s disconnect and prove it dead, as the lockout tagout procedure guide sets out.
The roof edge
Within 6 feet (1.8 m) of a low-slope roof’s edge, OSHA 1910.28(b)(13) asks for a guardrail, net, travel restraint or fall arrest. The roof inspection checklist has the rest.

When a check fails

If it is unsafe (a cracked heat exchanger, a burnt wire, a motor that smells hot), shut the unit down and tag it. Otherwise write a work order the same day, on paper or in facility maintenance software, with the failed reading in it.

Your own technician can do the monthly checks and most of the quarterly service. Filters and coils need more than this on a dusty roof or beside a kitchen exhaust. This list is a starting point, not a substitute for training or the maker’s manual.

What the standards sayASHRAE 180 and 62.1, EPA refrigerant rules, Canada's halocarbon rules.
  • ANSI/ASHRAE/ACCA Standard 180 sets minimum inspection and maintenance tasks for commercial building HVAC, in tables by type of equipment. It binds you only where a contract, code or owner adopts it. ASHRAE sells Standard 180.
  • ASHRAE Standard 62.1, the ventilation standard, has a maintenance table its committee based on Standard 180. The lines marked 62.1 above come from that table as published in Addendum e to the 2013 edition, free from ASHRAE. The 2022 edition numbers it Table 8-1, and its Addendum h replaced it in 2025 with a table of inspection tasks, so the edition your jurisdiction adopted is the one that counts.
  • Refrigerant. EPA requires Section 608 certification for anyone who maintains, services, repairs or disposes of equipment that could release refrigerant. Since January 1, 2026, EPA’s leak repair rule for HFC appliances covers systems holding 15 pounds or more, with a 10 percent leak rate threshold for comfort cooling, but leaves out the residential and light commercial air conditioning subsector; your technician can say which of your systems it covers. In Canada, the Federal Halocarbon Regulations, 2022 cover federal systems and those on federal or Indigenous lands, and the provinces regulate the rest.

None of this is legal advice, and no checklist makes a building compliant.

HVAC visits in Maintensor: one procedure per visit

Set each unit up as an asset with its nameplate, and build one procedure per visit: monthly, quarterly, spring and fall. There is no ready-made library, so you type the checks in once.

  • Make each line an Inspection check, answered Pass, Flag or Fail, and each reading a Number step. A Number step has no units or limits, so put them in its name: “Compressor amps L1 (nameplate RLA 18.6)”.
  • Attach the monthly procedure to a work order on the unit that repeats monthly, with yearly repeats for the start-ups. When one is completed, the next is created with a blank checklist.
  • A Fail answer asks for a note and a photo, then offers a follow-up work order and Mark asset down, which sets the unit to Down.
The checklist on a monthly air handler service: two steps before starting, both done, and the pre-filter check passed with the technician's note.
The monthly service of an air handler in progress: two steps before starting are done, and the pre-filter check passed with the technician's note.

What it does not do: a reading lives only on the work order it was taken on, with no chart of readings, so comparing July with June means opening June’s completed work order. Work comes due by the calendar, never by run hours, and only Admins and Full users answer checklists. The facility maintenance software page shows the whole building’s setup.

Questions

What people also ask.

More in the checklists, or see the whole product on the features page.

How often should commercial HVAC equipment be serviced?

Most rooftop units and air handlers get a monthly look at filters and drains, a quarterly service, and two seasonal start-ups: cooling in spring and heating in fall. The maintenance table in ASHRAE Standard 62.1, as its 2016 addendum set it, asks for filter pressure drop checks at least quarterly and fan belt checks twice a year. The maker's manual or a dusty site can call for more.

Who is allowed to work on the refrigerant in a rooftop unit?

In the United States, anyone who maintains, services, repairs or disposes of equipment that could release refrigerant must hold EPA Section 608 certification. Type II covers high-pressure systems such as rooftop units and split systems; an apprentice may work under a certified technician's close, continual supervision. In Canada, federal and provincial halocarbon rules limit the work to certified people.

What readings should a technician record on an HVAC service?

Return and supply air temperatures after a steady run, the outdoor temperature, the filter pressure drop, and the amps on each leg of the fan motors and compressors beside their nameplate figures; on heating, the temperature rise. Take the same readings every time, because a reading means most next to last month's.

Should filters be changed on a schedule or by pressure drop?

With a gauge, change filters at the pressure drop the filter maker or the building's operations manual gives, not by the calendar; without one, a fixed interval is the fallback. A reading near zero is a fail too: a filter is missing, air is getting around the bank, or the gauge tube has come off.

Run one building through it.

Start the trial, add one building with its floors, rooftop units and boiler, and invite the people who report problems as requesters, free on every plan.

30-day free trial. No credit card.