Lockout tagout procedure: the steps, and a template for one machine

A lockout tagout procedure is the written sequence for one machine: shut it down, isolate every energy source, put on locks and tags, release stored energy, prove it is dead, and later return it to service.

By MaintensorUpdated 12 min read

Key points

  • The eight steps follow the order of OSHA's rule, 29 CFR 1910.147, from preparing to returning to service.
  • Each machine's procedure names its own energy sources and isolating devices; one generic procedure cannot meet the rule.
  • A stop button or an emergency stop is never the isolation point. Lock the disconnect, breaker or valve.
  • OSHA requires an inspection of each procedure at least yearly, by an authorized employee who does not use it.
  • In Canada, your province, territory or the federal government sets the rule; the national standard is CSA Z460-20.

Lockout tagout steps, in order

In the US, OSHA’s rule at 29 CFR 1910.147 requires a written procedure for most machines your crew services. These eight steps follow paragraph (d) of the rule, with the notice to affected employees that (c)(9) requires and paragraph (e)’s release at the end.

  1. Prepare. Know each energy source on the machine, its magnitude, its hazards and how to control it ((d)(1)).
  2. Notify. Tell the affected employees before the locks and tags go on ((c)(9)).
  3. Shut down. Stop the machine by its normal procedure, in an orderly shutdown ((d)(2)).
  4. Isolate. Operate every energy isolating device: the disconnect, the breaker, the valve ((d)(3)).
  5. Lock and tag. A lock and tag on each isolating device, each authorized person with their own. In a group lockout, each person’s own lock goes on the group lock box ((d)(4), (f)(3)).
  6. Release stored energy. Bleed, drain, block, discharge or let cool, and keep checking if it can build back up ((d)(5)).
  7. Verify zero energy. Before work starts, make sure everyone is clear, try the normal start, read the gauges, test for voltage where the work needs it, then return the controls to Off ((d)(6)).
  8. Return to service. Tools out, guards on, people clear, each person removes their own lock, and affected employees are told before the start ((e)(1) to (e)(3)).

This is the outline, not the procedure

Each machine’s written procedure fills every step in with its own devices, which is what the rest of this guide covers. Neither the outline nor the procedure replaces the training the rule requires.

Before you write: walk the machine

  1. Find every energy source. The main electrical supply, control power that may come from another panel, compressed air, hydraulics, steam or water under pressure, gas, gravity (a raised platen or a hopper), springs, heat, chemicals in lines, and capacitors in drives.
  2. Write down the magnitude. Volts and phase, psi, temperature, the weight of what could fall.
  3. Find each isolating device and tag it. The label on the disconnect, breaker or valve matches its name in the procedure.
  4. Check each one takes a lock. After January 2, 1990, new machines, and machines replaced, given a major repair, renovated or modified, must have isolating devices designed to accept a lockout device ((c)(2)(iii)).
  5. Look for what restarts on its own. Compressors on pressure switches, pumps on float switches, timers.
  6. Photograph each isolation point, locked and tagged, for the procedure and for training.

A stop button is never the isolation point

OSHA’s definition excludes push buttons, selector switches and other control circuit devices, so a stop button or an emergency stop is never the isolation point.

Electrical work has its own rules

Opening a disconnect and testing for voltage can themselves expose a person to shock and arc flash. Your electrical safety program decides who may open a disconnect. Have a person qualified for electrical work do the testing and any work on live or possibly live parts, under NFPA 70E in the US or CSA Z462 in Canada.

Lockout procedure template: the three parts

The header:

Field Fill in
Machine and tag Name, tag number, size
Location Building, area, room
Procedure number and version Number, version, date
Purpose and scope The jobs this covers, and the ones it does not
Authorized employees Who may apply locks, by trade or name
Affected employees Who is told before and after
Devices needed Locks per person, hasps, valve lockouts, blocks, tags
Written, reviewed, approved Names and dates

The energy sources: one line for each source, numbered E1, E2 and on, with these columns.

EnergyElectrical, compressed air, hydraulic, steam, gravity, springs, heat, an automatic restart.
MagnitudeVolts and phase, psi, temperature, the weight that could fall.
Isolating device and locationThe disconnect, breaker or valve, by its tag, and where it is.
Lock or devicePadlocks and hasp, a valve lockout, a block.
Stored energy, how to release itBleed, drain, block, discharge, let cool.
How to verifyThe try-start, a gauge at zero, a voltage test.

The sequence: the eight steps above, each written for this machine, plus how protection passes from the off-going person to the oncoming one at a shift change ((f)(4)). Name the procedure on every work order for a job on that machine, so nobody has to remember to look for it.

Lockout procedure example: a rotary screw air compressor

Everything here is invented to show the shape: the plant, the compressor, its tags and its figures. Your machine’s manual and a walk-down of your own machine decide the content.

ExampleEC-C2: lockout for compressor C-2

Field Entry
Machine and tag C-2, 25 hp (18.6 kW) rotary screw compressor, with receiver R-2, 240 gal (about 900 L)
Location Compressor room, Riverside Plant
Procedure EC-C2, version 2
Scope Oil, filter and separator changes, any work inside the enclosure, work on R-2. Not covered: the 480 V feeder (electricians’ procedure EC-MCC1).
Authorized Maintenance mechanics trained in lockout: Ben Carter, James O’Neil
Affected Line 1 and Line 2 leads, who lose air if C-1 cannot carry the load
Devices One padlock per person per device, one hasp, one ball valve lockout, tags
# Energy Magnitude Isolating device Device Release Verify
E1 Electrical, main and control 480 V, 3-phase; 120 V control from C-2’s own transformer Disconnect DS-12, wall left of C-2 Hasp, padlocks, tags This fixed-speed machine stores none. A variable-speed drive’s capacitors do: wait the time on its label Start does nothing, then a voltage test by a qualified person
E2 Compressed air: plant header and receiver R-2 125 psi (860 kPa) Ball valve V-12, between R-2 and the header Valve lockout Open drain D-2 on R-2 Gauge P-2 at 0
E3 Compressed air in the separator tank up to 125 psi None: blows down at stop None Wait for blowdown Sump gauge at 0
E4 Heat Oil and discharge piping hot after running None None Let it cool for the time in the manual Surface thermometer before hands go in
E5 Automatic restart Starts on its own when pressure falls Controlled by E1 Same as E1 None Covered by E1
  1. Prepare. Read EC-C2. Hazards: 480 V, air at 125 psi, hot oil, automatic start.
  2. Notify. Tell the Line 1 and Line 2 leads that C-2 is coming off. Confirm C-1 is running.
  3. Shut down. Press Stop on C-2’s panel and wait for the unload and blowdown to finish.
  4. Isolate. Open DS-12. Close V-12.
  5. Lock and tag. Each mechanic puts their own lock and tag on the DS-12 hasp and on the V-12 lockout.
  6. Release. Open D-2 until P-2 reads 0 psi, and leave it open. Confirm the sump gauge reads 0. Let the machine cool.
  7. Verify. With everyone clear, press Start: nothing runs. A dark display proves little, because a blown control fuse looks the same. P-2 and the sump gauge read 0. Return the start switch to Off. Before anyone touches electrical parts, a person qualified for electrical work tests for voltage.
  8. Restore. Tools and rags out, panels on, D-2 closed, start switch at Off, everyone clear. Each mechanic removes their own lock. Tell the line leads the locks are off, then open V-12 slowly so the empty receiver does not pull down plant air, close DS-12 and start C-2.
  9. Shift change. The off-going mechanic’s lock stays on until the oncoming mechanic’s lock is on.

The routine service on a machine like this is in our air compressor maintenance checklist, which starts with locking out.

What OSHA requires in a written lockout procedure (29 CFR 1910.147)

The rule covers servicing and maintenance where an unexpected start-up, or a release of stored energy, could injure someone ((a)(1)(i)).

Work during normal production is covered if someone removes or bypasses a guard, or puts part of their body in a danger zone ((a)(2)(ii)). Minor tool changes and adjustments are outside the rule only if they are routine, repetitive, integral to production and done with other measures that give effective protection. Cord-and-plug equipment is outside it when unplugging controls the hazard and the plug stays in the hands of the person doing the work ((a)(2)(iii)(A)).

Paragraph (c)(4)(ii) says each procedure must clearly and specifically outline its scope, purpose, authorization, rules and techniques, and how compliance is enforced, including at least:

Paragraph The procedure must include In practice
(c)(4)(ii)(A) A statement of what the procedure is for The machine, its tag, and the jobs it covers
(c)(4)(ii)(B) Steps to shut down, isolate, block and secure the machine Each energy source, its isolating device and where it is
(c)(4)(ii)(C) Steps to place, remove and transfer locks and tags, and who is responsible Whose lock goes where; shift change; group lockout
(c)(4)(ii)(D) How to test the machine to verify the locks work The try-start, the meter, the gauge at zero

The procedure leans on the rest of the program:

(c)(5)Lock and tag devices that identify the person who applied them
(c)(7)Training
(c)(9)Telling affected employees before and after
(f)(1)If a machine must be powered to test or position it: clear tools and people, remove the locks, test, then shut down and lock out again
(f)(2)Contractors: you and the outside employer tell each other your lockout procedures
(f)(3)Group lockout
(f)(4)Shift changes
(c)(2)(ii) and (c)(3)Where an isolating device can take a lock, lockout is used unless the employer can show tagout gives full protection

The one exception to writing it down

Paragraph (c)(4)(i) lets an employer skip the written procedure for a machine only when all eight listed conditions hold. Among them: a single, easily identified energy source, no stored or residual energy, and one lock that isolates it completely. Any machine with stored air, hydraulic pressure, springs or a raised load fails it.

OSHA’s own model, Appendix A to 1910.147, is a typical minimal procedure; the template above adds a table of energy sources for one machine.

This page is information about the rule, not legal advice. It does not replace your energy control program, the training the rule requires, or a qualified person’s review of each procedure. Check the rule that applies to you (federal OSHA, your state plan, or your province) and the machine maker’s manual.

Lockout rules in Canada

Canada has fourteen jurisdictions, federal, provincial and territorial, each with its own health and safety law, as the Canadian Centre for Occupational Health and Safety explains. Your lockout rule is in your province’s or territory’s regulation, or in the federal one if your workplace is federally regulated.

The national standard is CSA Z460-20, “Control of Hazardous Energy: Lockout and Other Methods”, which CCOHS cites in its lockout guidance. The template is about the machine, so it fits either side of the border; the rule you check it against differs.

Testing it, and the yearly inspection

Before the procedure goes into use, walk it down on the machine with a second authorized person. Check that every device in the table is where the procedure says, that each carries the matching tag and takes a lock, and that the verify step really proves the machine is dead. Then train each authorized person on it. Our guide to writing a standard operating procedure covers testing written steps with someone who has never done the job.

The yearly inspection under (c)(6)

Paragraph (c)(6) requires a periodic inspection of each energy control procedure at least once a year, by an authorized employee other than the ones using it, to correct any deviations or gaps found. For lockout, it includes a review with each authorized employee of their responsibilities. The employer keeps a certification naming the machine, the date, the employees included and the person who inspected.

In practice: watch a real job, compare each step with the paper, check the energy table against the machine as it is today, and update the procedure where they differ. Between yearly inspections, the monthly safety inspection checklist asks whether locks and tags are at hand and each serviced machine has its procedure.

Mistakes that make a procedure fail

  • One generic procedure for the whole plant. “Turn off and lock out” names no isolating device, so it cannot meet (c)(4)(ii)(B).
  • A missed energy source. Control power fed from another panel, air trapped downstream of a closed valve, a platen held up by hydraulics.
  • No verification, or verification left switched on. Try the start, then return the control to Off before work begins.
  • Tags that do not match. The procedure says V-12; the valve has no label, or a different one.
  • Not updated after a change. A new receiver, a second compressor on the header, a rewired panel: each one changes the table.
  • Someone else’s lock removed. Under (e)(3), each device comes off by the person who put it on, except under the documented procedure the rule allows.

Lockout procedures in Maintensor, and what the app does not do

Like any checklist in Maintensor’s maintenance checklist software, EC-C2 can be built as a procedure and attached to each work order on C-2, so the lockout steps arrive with the job, once someone has attached it: instructions for the energy table, a checkbox for each lock, a photo of each locked device, a number for each gauge and a signature for each mechanic. A Fail on the try-start asks for a note and a photo before the next step, and offers a follow-up work order and Mark asset down.

The yearly inspection can be its own work order, repeating yearly, with a procedure for the certification. Give the inspector’s name a Text step, because a Signature step stores the drawn signature and the time, not which user signed.

When the machine changes, publish a new version of EC-C2. The procedure’s history lists each earlier version with who published it and when, though not its steps, so keep the reason for each change in the procedure’s description.

A procedure's history: created in August 2025, then version 1, version 2 in March and version 3, which is live now, each published by the maintenance manager.
A procedure's history: each version and who published it, and which one is live now.

What it does not do

Maintensor records what was done; it certifies nothing. It does not replace your energy control program, the training, the periodic inspection or the person who does it.

A required step does not block finishing: a person who may complete work can finish anyway, and the skipped step is written on the job’s history. It does not track who holds which lock, issue permits, or print the procedure to post at the machine. Steps hold words only, so keep the photos of each isolation point on the asset’s record.

It runs in a browser with no offline mode, so a compressor room with no signal still needs a copy posted at the machine, made outside the app.

Questions

What people also ask.

More in the blog, or see the whole product on the features page.

What must a written lockout tagout procedure include?

Under OSHA 29 CFR 1910.147(c)(4)(ii), the procedure states what it is for, gives the steps to shut down, isolate, block and secure the machine, gives the steps to place, remove and transfer locks and tags and who is responsible for them, and says how to test the machine to verify the locks work. In practice that means naming each energy source and its isolating device.

How often must lockout procedures be inspected?

OSHA 1910.147(c)(6) requires a periodic inspection of each energy control procedure at least once a year, by an authorized employee other than the ones using it. The employer keeps a certification naming the machine, the date, the employees included and the person who inspected. Canadian provinces set their own requirements.

What is the difference between lockout and tagout?

A lock physically holds an energy isolating device, such as a disconnect or a valve, in the off position until the person who put it on removes it. A tag is a warning only. Under OSHA's rule, a device that can take a lock is locked out unless the employer can show tagout gives full employee protection, with extra measures such as removing a valve handle or opening a second disconnect.

Does every machine need its own lockout procedure?

Each machine needs a procedure specific enough to name its own energy sources and isolating devices. The federal rule lets you skip writing one only when all eight conditions in 1910.147(c)(4)(i) hold, among them a single energy source, no stored energy, and one lock that isolates the machine completely. A compressor with an air receiver fails that test.

Is pressing the emergency stop enough to lock out a machine?

No. OSHA's definition of an energy isolating device in 1910.147(b) excludes push buttons, selector switches and other control circuit devices, and an emergency stop is one of those. Lockout goes on the device that physically cuts the energy, such as the disconnect switch, the breaker or the line valve.

Write the steps down once.