How a fault tree works: top event, gates and basic events
A fault tree has one top event, the thing you do not want, and under it the events that could cause it, down to basic events such as a part failing or a breaker tripping. Two gates join the levels:
- An OR gate means any one event below it is enough: a single failure gets straight through.
- An AND gate means all the events below it must happen together: this is where backups live, such as two boilers.
The US Nuclear Regulatory Commission’s 1981 Fault Tree Handbook (NUREG-0492) is a free, full reference, symbols included.
Fault tree example: no heat in a building with two boilers
A made-up building has two boilers, B-1 and B-2, either of which can heat it alone; a duty pump, P-1, with a standby, P-2, that should start when P-1 stops; and one gas service, one boiler room power panel and one controller with an outdoor sensor.
Gas and power sit at the top, not under each boiler, because one closed gas valve takes out both boilers at once, and one tripped breaker can take out the boilers and the pumps together. A cause shared by both sides of a backup is a common cause, and exposing it is the first thing a fault tree is good at.
Reading the tree, with numbers
Follow the OR gates from the top: gas, power, the controller and the outdoor sensor can each stop the heat alone. Those are the single points of failure. Each is a minimal cut set, the smallest group of failures that causes the top event on its own; a fault on B-1 together with a fault on B-2 is another.
Some made-up numbers for a 180-day heating season (4,320 hours): each boiler is out 2% of the time, independently of the other, and the single controller 0.5%.
0.02 × 0.02 × 4,320 h
0.005 × 4,320 h
21.6 h ÷ 1.73 h
So the backup boiler is doing its job, and the next dollar goes to the parts with no backup: a spare outdoor sensor, a yearly check of the gas valve train by a qualified technician, and a monthly test that P-2 really starts when P-1 is stopped.
Draw a tree like this for the three or four systems where a stop hurts most.
Fault tree vs 5 whys and FMEA
- The 5 whys follows one chain from one problem, in under an hour: enough for most breakdowns.
- A fault tree follows every branch, in a few hours for a small system: for systems with backups.
- FMEA works up from each part of one machine, before anything has failed.
The root cause analysis guide sets these tools side by side.
A system’s assets and tests in Maintensor
Maintensor has no fault tree tool, but as equipment maintenance software it can keep a tree’s system together. An asset can sit inside another (its Parent asset), so a boiler plant, its boilers and its pumps are recorded as one system, and the standby pump’s changeover test can be a work order that repeats every month.