Electric motor maintenance checklist

An electric motor maintenance checklist for a three-phase induction motor lists a look, listen and temperature check each shift, weekly oil and starter checks, voltage and current on each leg every three months, and an insulation test every six months.

Free, no sign-up. Print it, or type into the Word file.

By MaintensorUpdated

Page 1 of the blank electric motor maintenance checklist: the motor and visit, then the checks for every shift, weekly and monthly, and every 3 months, each with a box for OK and Fail and a line for a note.
Page 1 of 2

The checks, by visit

One sheet per motor and visit, for a three-phase AC induction motor up to a few hundred horsepower, driving a pump, a fan, a conveyor or a compressor. A failed check gets a work order with the reading and a photo, and the motor’s manual wins where it differs.

Every shift: listen, smell and take its temperature7 checks

  • Sound
  • Smell
  • Frame and bearings, infrared thermometer
  • Feet and base
  • Fins, fan cover, air openings
  • Coupling or belt guard
  • Starter or drive

Weekly and monthly: oil, starter, start-up time and the drive5 checks

  • Weekly: Oil level, oil-lubricated bearings
  • Weekly: Shaft, for oil leaking
  • Weekly: Starter, switches, fuses, covers closed
  • Weekly: Time to reach speed
  • Monthly: Belts or coupling, with the guard

Every 3 months: voltage and current on each leg4 checks

  • Voltage, each pair of lines
  • Voltage against the nameplate
  • Current on each leg, at normal load
  • Bearing temperature and vibration, written down

Every 6 months: clean, tighten and test the insulation5 checks

  • Clean fins, fan and air paths
  • Grease in the bearings, checked
  • Terminal box connections
  • Feet, shims and grout
  • Insulation resistance

Yearly: grease, an infrared scan and the lockout procedure5 checks

  • Regrease the bearings, unless the maker says sooner
  • Infrared scan of starter and terminal box, under load
  • Alignment at the coupling, belt tension
  • Lockout procedure, inspected by someone who does not use it
  • A plan for each motor that would stop the plant
What counts as a fail, check by checkThe full tables, and where each interval comes from.

The intervals follow Table 1 of the Department of Energy’s motor and drive sourcebook (page 29), which lists weekly, six-monthly and yearly tasks. In the last column, Rule links the regulation, Maker is the motor maker’s manual or NEMA MG 1, the motor makers’ standard, DOE is that sourcebook, and Practice is common plant practice.

Every shift: listen, smell and take its temperature

Check Fail when Basis
Sound A new hum, growl, squeal or knock Practice
Smell Hot varnish or burning: stop it Practice
Frame and bearings, infrared thermometer Hotter than usual at the same load Practice
Feet and base Shaking more than usual; a loose bolt Practice
Fins, fan cover, air openings Caked with dust, blocked, a dented fan cover Maker
Coupling or belt guard Missing or loose Rule
Starter or drive A fault showing, a trip that repeats Practice

The TECO-Westinghouse motor manual says dirt on the external fan of a fan-cooled motor leads to unbalance and vibration, and that dirt on screens and louvers restricts the air. The guard row rests on OSHA 1910.212(a)(1), which requires guarding against rotating parts.

Weekly and monthly: oil, starter, start-up time and the drive

When Check Fail when Basis
Weekly Oil level, oil-lubricated bearings Below the mark DOE
Weekly Shaft, for oil leaking Oil on the shaft or inside DOE
Weekly Starter, switches, fuses, covers closed A hot smell, buzzing, a fuse blown again DOE
Weekly Time to reach speed Longer than usual DOE
Monthly Belts or coupling, with the guard Cracked belt, worn insert, loose guard Rule

1910.219(p)(1) requires power-transmission equipment to be inspected at intervals not exceeding 60 days. A motor that is slower to come up to speed than it used to be is carrying more load, seeing low voltage, or wearing.

Every 3 months: voltage and current on each leg

Check Fail when Basis
Voltage, each pair of lines Unbalance over 1% Maker
Voltage against the nameplate Outside 10% of rated Maker
Current on each leg, at normal load A leg over nameplate amps, or legs further apart than last time Practice
Bearing temperature and vibration, written down Up from the motor’s baseline Practice

The limits are NEMA MG 1’s, listed with the worked example below. A vibration reading taken at the same point each time catches bearing wear early.

Every 6 months: clean, tighten and test the insulation

Check (locked out) Fail when Basis
Clean fins, fan and air paths Dirt left in the air paths Rule
Grease in the bearings, checked Hard, dark, gritty or leaking out DOE
Terminal box connections Loose, discolored or burnt DOE
Feet, shims and grout A rocking foot, a loose bolt, cracked grout DOE
Insulation resistance Below the maker’s minimum, or falling DOE

Vacuum, or blow out with dry air: 1910.242(b) allows compressed air for cleaning only below 30 psi, with chip guarding and protective equipment, and the DOE table says 25 to 30 psig.

The sourcebook also warns about soft foot: a mounting foot that does not sit flat lets the motor flex under load, which misaligns it and wears the bearings (page 30).

Yearly: grease, an infrared scan and the lockout procedure

Check Fail when Basis
Regrease the bearings, unless the maker says sooner Not done DOE
Infrared scan of starter and terminal box, under load A connection hotter than its neighbors DOE
Alignment at the coupling, belt tension Outside the maker’s limit Practice
Lockout procedure, inspected by someone who does not use it Not done this year Rule
A plan for each motor that would stop the plant No spare, and no repair shop picked DOE

The scan row comes from the voltage unbalance tip sheet, which suggests annual thermographic inspections; infrared thermography explains what the camera finds. The DOE’s tip sheet on motor life says to choose a motor repair service center before you need one.

The lockout row is 1910.147(c)(6), at least once a year. How much grease, and how to work out the interval from a bearing maker’s chart, is in the bearing lubrication guide.

Voltage unbalance example: three readings worked out

The DOE sourcebook lists NEMA MG 1’s usual service conditions for a motor (page 27):

VoltageWithin 10 percent of rated.
Voltage unbalance1 percent or less.
FrequencyWithin 5 percent.
Air around the motorBetween 0 and 40 °C.

The DOE’s tip sheet on voltage unbalance says to check voltages at the motor terminals periodically, and that above 1 percent the motor must be derated.

ExampleA cooling tower fan motor, read at its starter

A made-up 480-volt motor driving a cooling tower fan, nameplate 52 amps. The electrician reads, at its starter, under normal load:

Reading A to B B to C C to A
Voltage 482 V 478 V 470 V
Reading Leg A Leg B Leg C
Current 40 A 44 A 48 A

NEMA’s definition, as the DOE tip sheet gives it: unbalance is 100 times the largest difference from the average voltage, divided by the average.

  1. Average voltage: (482 + 478 + 470) ÷ 3 = 476.7 V.
  2. Largest difference: 476.7 minus 470 = 6.7 V.
  3. Unbalance: 6.7 ÷ 476.7 × 100 = 1.4 percent. Over the 1 percent limit.
  4. Current, the same way: average 44 A, largest difference 4 A, so 9.1 percent, about six and a half times the voltage figure. The tip sheet says current unbalance may be 6 to 10 times the voltage unbalance.
  5. Heat: the tip sheet’s estimate multiplies the motor’s temperature rise by 1 + 2 × 1.4² ÷ 100, about 1.04. A motor with an 80 °C rise runs about 3 °C hotter, and the same sheet says winding insulation life halves for every 10 °C.

What it shows. No leg is over 52 amps, so the motor is not overloaded: the supply is uneven.

Where to look. The electrician reads the same three voltages at the panel feeding it. If the unbalance is there too, the cause is upstream; the tip sheet’s list starts with single-phase loads spread unevenly across the phases and faulty power factor correction equipment.

If the panel is balanced and the motor is not, look between them: a loose connection or a worn contactor pole. Fix it, then read all six numbers again.

Insulation resistance: what a megohmmeter test tells you

The test puts a DC voltage, typically 500 or 1,000 V, on the winding and measures the resistance to ground. The DOE sourcebook says expected values are in megohms, as set out in IEEE Standard 43, and that wet insulation is a common cause of low readings (page 28).

The minimum is the maker’s. ABB’s drive installation guide asks its own motors for more than 100 megohms at 25 °C, measured at 1,000 V DC, and sends other motors to their maker’s instructions.

Energizing a motor with weak or wet insulation can lead to catastrophic failure, the sourcebook warns: dry it and test again. On a drive-fed motor, ABB’s guide says to measure the insulation only with the motor cable disconnected from the drive.

The number moves with temperature. The TECO manual corrects readings to 40 °C, and as an approximation for a new winding, resistance halves for each 10 °C (18 °F) rise.

ExampleTwo readings, brought to the same temperature

Made-up readings from one motor.

Test Winding temperature Reading Brought back to 20 °C
Last spring 20 °C 850 megohms 850 megohms
This summer 30 °C 400 megohms About 800 megohms

No real change. Without the temperature written down, it looks like the winding lost half its insulation.

Motors on a variable frequency drive

On a drive-fed motor, listen for new bearing noise, and check a grounding brush, where fitted, at its maker’s interval.

What a drive does to a motorVoltage spikes, current through the bearings, and running slow.

A drive changes three things, by the DOE’s tip sheet on motors and drives and the motor’s own data:

Voltage spikesThe drive's fast pulses put spikes on the winding, and over 1,000 V they can short turns of a coil.
Bearing currentCurrent pushed through the bearings causes damage called fluting, which insulated bearings or a shaft grounding brush reduce or stop.
Slow runningA fan-cooled motor's fan turns with its shaft, so one run slowly for long hours moves less air: the motor's data says how slow it may run.

Before you start

Who does what
Anyone on the crew can do the shift checks, from outside the guards with no covers off. Readings at live terminals, insulation tests and work inside the terminal box are for a qualified electrician.
Hot surfaces
Use a thermometer, not a hand: a motor’s surface can be hot enough to burn.
Drives hold a charge
After switching off the power, wait 5 minutes for the drive’s capacitors to discharge before any work, as ABB’s guide says. Other drives give their own wait.

When a check fails

Smoke or a burning smell, a bearing screaming, or a motor that trips again after one reset: stop it, lock it out and call the electrician. Do not keep resetting an overload.

Anything else gets a work order with the reading and a photo.

Electrical safety rules for motor work

OSHA 1910.333(a)(1) requires live parts to be deenergized before work on or near them, unless that adds hazards or is infeasible. Reading current and voltage on a running motor is work near live parts, so it is for a qualified person; everything else is done locked out under 1910.147.

The rules in detailQualified persons, NFPA 70E, stored energy in a motor, and Canada.

A qualified person is defined in 1910.399, and works with the protective equipment that NFPA 70E, the standard for electrical safety in the workplace, sets out.

Paragraph (d)(5) of 1910.147, on stored energy, applies to a drive’s charged capacitors and to a load that can turn the shaft, such as a fan windmilling in a draft.

The lockout/tagout procedure guide covers writing the steps for one machine, and the electrical inspection checklist covers the panels feeding the motors. In Canada, CSA Z462 is the workplace electrical safety standard, and provinces have their own rules.

This is information, not legal advice: check the rules that apply to you and the motor maker’s manual.

Motor checks in Maintensor: six readings and a follow-up job

Make the motor an asset with its nameplate, and write the full-load amps and the bearing numbers in its description. Put it under the machine it drives with Parent asset: the pump maintenance checklist suggests the same for a pump and its motor.

  • Build the quarterly procedure as six Number steps, three voltages and three currents, then one more for the unbalance the electrician works out: the app records the numbers but computes nothing. Write the unit and limit into the step: “Voltage unbalance, % (fail over 1)”.
  • The six-monthly service opens with a Checkbox marked Required for the lockout, then a Number step for insulation resistance and one for the winding temperature. An outside electrician’s report goes on the work order as an attachment.
  • Set the quarterly work order to repeat Monthly, Every 3, and the six-monthly one Monthly, Every 6. A Fail asks for a note and a photo, then offers a follow-up work order and Mark asset down.
Run mode on a failed check: Fail is chosen for the pulley alignment, the finding is written, a photo is asked for, and a follow-up work order is offered.
Run mode on a failed check: Fail chosen for a pulley alignment, the finding written, a photo asked for, and a follow-up work order offered. A failed motor check runs the same way.

What it does not do: there are no meters or sensors, and a Number step has no unit or limits. Its value stays on that work order’s Checklist, not on the asset or in Reporting, so comparing this quarter’s currents with the last means opening last quarter’s work order.

Only Admins and Full users answer checklists. The manufacturing maintenance software page shows the rest of a plant’s setup.

Questions

What people also ask.

More in the checklists, or see the whole product on the features page.

How often should an electric motor be greased?

At the interval and amount on the motor's lubrication plate or in its manual. Where the maker says nothing more specific, the DOE's motor sourcebook checks the grease every six months and regreases once a year. One motor maker halves its intervals for belt drives and for dirty, hot or humid rooms. A motor with sealed bearings has no grease fitting and is never greased.

What is a good insulation resistance reading for a motor?

The minimum comes from IEEE 43 and the motor's maker. ABB, for its own motors, asks for more than 100 megohms at 25 °C, measured at 1,000 V DC. The trend matters as much as the number: readings fall as a winding warms or gets damp, so compare each test with the last one at the same temperature, and dry a wet motor and test again before running it.

Should a failed motor be repaired or replaced?

It depends on size. The DOE says the smallest standard motors are replaced when a key part such as a bearing fails, larger standard motors up to 20 or 50 horsepower may get new bearings but are often scrapped after a winding failure, and still larger motors may be rewound. Decide before the failure, with a repair shop picked in advance.

Run one line's maintenance through it.

Start the trial, add the machines on one line with their recurring jobs and checklists, and let the crew close work from the floor on a phone.

30-day free trial. No credit card.