Backflow testing log and checklist

Backflow testing is a check, by a certified tester, that each assembly still stops water from the building's pipes flowing back into the drinking water supply. Your water supplier or city sets how often: usually once or twice a year.

Free, no sign-up. Print it, or type into the Word file.

By MaintensorPublished

The blank backflow testing log, one landscape page: the building and its water supplier, a line for each assembly with its type, serial number, last test, result, tester, report sent and next due date, then the six checks of the look between tests, each with a box for OK and Fail.

What the log holds

One landscape page for a building, kept for the year: a line for each assembly and its test, and the look your staff take between tests. The tester’s own report goes with it.

Each assemblyWhere it is, its type and size, its serial number, the day it was tested, pass or fail, the tester and their certificate number, the day the report went to the water supplier, and when the next test is due.
A failed testTwo lines: the failed test, then the test again after the repair.
The look between testsSix checks your own staff make, monthly or as often as you choose, below.

ExampleA year's log: three assemblies

A made-up food plant in Oregon, with three testable assemblies. Its water supplier asks for a test every year. A certified tester comes in May; Jessica Turner keeps the log.

Assembly Type Tested Result Note
BF-1, main supply in the boiler room RP, 2 in May 12 Fail Relief valve spilling at the test. First check cleaned, retested May 14: pass
BF-2, fire sprinkler supply Double check, 6 in May 12 Pass Monitoring company told before the water was shut off
BF-3, lawn irrigation PVB, 1 in May 12 Pass

BF-1. Jessica had noted water dripping from its relief valve on her April look. The test found the first check valve fouled. Both lines go on the log, and both results to the water supplier.

BF-2. A test shuts the sprinklers’ water off while it runs, so the monitoring company and the fire department are told first, as for any sprinkler shutdown.

The look between tests

The test belongs to the certified tester. Between tests your staff only look: nothing is opened, closed or taken apart.

The look between tests6 checks

  • RP relief valve not running with water
  • Each assembly reachable, nothing stored against it
  • Shutoff valves on each side open
  • No leaks or damage; test cocks capped
  • Kept from freezing: enclosure closed, heat on
  • Test tag on each assembly, last test date on it
What counts as a fail, check by checkThe full table, and where each check comes from.

“Practice” means common practice and no rule.

Check Fail if Source
RP relief valve not running with water Water running from the relief port, not just a short spill after a pressure drop EPA Cross-Connection Control Manual (how the relief valve works); NFPA 25, 13.7.1 on a sprinkler supply (weekly)
Each assembly reachable, nothing stored against it Stock, pallets or plants in the way of the test Practice
Shutoff valves on each side open A valve left shut after a test or a repair Practice
No leaks or damage; test cocks capped A drip at a joint, a cracked body, a cap missing Practice
Kept from freezing: enclosure closed, heat on An open enclosure door, a heater off in cold weather Practice
Test tag on each assembly, last test date on it No tag, or the date past the interval Toronto (a tag on each device with its test history)

How often, and who sets it

No national rule sets how often a backflow assembly is tested. Your water supplier sets it, or your state, city or municipality in its plumbing code or a bylaw, along with who may test. The EPA’s own summary: “Testing intervals typically are annual, semi-annual, or risk-based.”

Check By United States Canada
Test each testable assembly A certified tester As your water supplier or state sets: usually yearly, sometimes twice a year for an RP As your municipality sets: at least yearly in Toronto
Test after installing or repairing one A certified tester As your supplier sets; the EPA’s model ordinance has the owner pay for the retest Toronto: at installation, and within 72 hours of a cleaning, repair or replacement
On a sprinkler supply: look at an RP assembly Your staff Weekly (NFPA 25) Weekly (NFPA 25, through the National Fire Code)
On a sprinkler supply: the yearly flow test The sprinkler company Yearly (NFPA 25) Yearly (NFPA 25)
The look between tests Your staff Monthly, as practice Monthly, as practice

The inspection calendar below has no preset for the test itself: you choose the interval your water supplier gives you.

The kinds of assembly

The EPA’s Cross-Connection Control Manual and its 2007 paper describe them. Which one a line needs depends on what could flow back through it, and your water supplier decides.

Reduced pressure (RP)Two check valves with a relief valve between them that spills water out rather than let it flow back. Where the hazard is high. Tested.
Double check valve assemblyTwo check valves, no relief valve. Where water could be pushed back under pressure. Tested.
Pressure vacuum breaker (PVB)Stops water being siphoned back, for a low hazard. Tested.
Atmospheric vacuum breakerA small device on a single fixture or hose bib. It cannot be tested once installed, so it has no line on the log.
Air gapA space of open air between the water outlet and what it fills. Nothing to test; the look checks that nobody has closed the gap, with a hose dropped into a tank.

Before you start

Who
The test: a certified tester your water supplier accepts. The look: your own staff. Repairs: a plumber, or the tester where they repair too.
Water off
A test shuts the water off through that assembly for a while. Warn the people it serves, and on a sprinkler supply tell the monitoring company first.
The record
Keep the log and the tester’s reports. Toronto asks for copies kept on site for seven years.

When a check fails

Water running steadily from a relief valve, a leak, a failed test: call your tester or plumber, and write a work order so the fix is tracked. A repaired assembly is tested again, and the result goes to the water supplier.

This log is a starting point to adapt with your water supplier’s rules and your tester. It is information, not training, and it does not replace the test.

Add it to an inspection calendar

Put these checks, and the rest of the building's, on a year plan with the usual minimums for the United States or Canada, then print it or add it to your calendar: open the inspection calendar with backflow preventers ticked.

What the rules say

In the United States, the water supplier runs a cross-connection control program under its state’s rules, and the plumbing code your state or city adopts sets the rest. In Canada, your municipality or water supplier sets it, usually in a bylaw.

What the rules sayWhat was read, and the records to keep.
  • The EPA. The Cross-Connection Control Manual (2003) describes the assemblies, says an atmospheric vacuum breaker cannot be tested once installed, and gives a model ordinance: the owner pays for the permits, the yearly or twice-yearly tests and the retest after a failure, and the supplier keeps a list of certified testers. Its 2007 issue paper finds intervals “typically are annual, semi-annual, or risk-based”, with Boston testing RP assemblies twice a year and double check assemblies once a year, as its state asks. It adds that systems put an atmospheric or pressure vacuum breaker on a low hazard, a double check where water could be pushed back under pressure, and an RP where the hazard is high.
  • Toronto. The backflow prevention program: industrial, commercial, institutional and larger residential properties; a test at installation, within 72 hours of a repair, and at least once a year; by a certified Cross Connection Control Specialist, who reports online; a test tag on each device; records kept on site for seven years.
  • Fire sprinkler supplies. NFPA 25 adds a weekly look at a reduced pressure assembly (13.7.1) and a yearly forward flow test (13.7.2), whatever the water supplier asks.

None of this is legal advice, and no log makes an assembly compliant.

Backflow tests in Maintensor: each assembly an asset

Make each assembly an asset in its location, with its type and serial number in the description. An asset’s Work orders tab then lists every test, open and done.

  • The test. A work order for each assembly that repeats yearly, or as your supplier sets, with the tester’s report attached and the readings in its notes.
  • The look. One procedure with an Inspection check for each line, answered Pass, Flag or Fail, on a work order that repeats monthly. There is no ready-made library, so you type the checks in once.
  • A Fail asks for a note and a photo, then offers a follow-up work order for the repair.
A conveyor's work orders: four open with their due dates, a note that a V-belt has been used on it 10 times this year, and the latest finished jobs with their parts cost.
An asset's work orders: four open with their due dates, and the latest finished jobs with their parts cost. Each backflow assembly keeps its tests the same way, here shown on a conveyor.

What it does not do: Maintensor does not send the test report to your water supplier, and it does not know a tester’s certificate is current. Only Admins and Full users answer checklists, so whoever takes the look needs a user seat. It records what was checked; it certifies nothing. The facility maintenance software page shows the rest of a building’s setup.

Questions

What people also ask.

More in the checklists, or see the whole product on the features page.

How often does a backflow preventer need to be tested?

As often as your water supplier, city or state sets: no national rule does. The EPA puts it plainly: testing intervals are typically annual, semi-annual or risk-based. Toronto, for one, asks for a test at least once a year, at installation, and within 72 hours of any repair. Ask your water supplier for yours.

Who can test a backflow preventer?

In most places, a certified backflow tester, and your water supplier says which certificate it accepts. The EPA's model program has the supplier keep a list of certified testers, so the supplier is the first place to ask for one. In Toronto the tester holds a Cross Connection Control Specialist certificate; plumbers, engineers and sprinkler fitters can hold it.

Who pays for backflow testing?

The property owner, in the programs the EPA describes: its model ordinance makes the owner responsible for the permits, the yearly or twice-yearly tests, and the retest after a failure. In Toronto the tester reports the result to the city online; elsewhere, ask your supplier who sends it.

Why is water coming out of my backflow preventer?

On a reduced pressure (RP) assembly, the relief valve lets water out whenever the pressure inside comes within a few pounds of the supply's, as the EPA's manual describes it. That is its job, and a short spill when the supply pressure drops is expected. Water running from it steadily means something inside is not holding: call your tester or plumber.

Run one building through it.

Start the trial, add one building with its floors, rooftop units and boiler, and invite the people who report problems as requesters, free on every plan.

30-day free trial. No credit card.